Medidor multifunción LCD
Información básica
Modelo: SCD924Z-9XY-PQH
Descripción del producto
1.CCC CE aprobado
2. Entrada de CC y salida de CC
Precio 3.low con alta calidad
Medidor multifunción LCD
1. Opción de modo de salida:
X: Instrumento de visualización sin función de salida
K: Salida de contacto de relé
B: Salida de transmisión analógica de la cantidad
T: Interfaz de comunicación RS485
S: salida de contacto de relé + interfaz de comunicación RS485
D: Salida de transmisión analógica de la cantidad + interfaz de comunicación RS485
N: Salida de contacto de relé + Salida de transmisión analógica + Interfaz de comunicación RS485
2..Producto Función
Product Function |
SCD912E-9S4 |
|
Real-time Measurement |
Three-phase Voltage |
√ |
Three-phase Current |
√ |
|
Power |
√ |
|
Frequency |
√ |
|
Energy Metering |
Active Energy |
√ |
Reactive Energy |
√ |
|
Bi-directional Metering |
√ |
|
Demand Value |
U I P Q Slip |
√ |
Energy Pulse |
Passive Node |
2 |
Transmission Output |
4-20mA/0-5V |
2 |
Switch Input |
Passive Node |
6 |
Relay Output |
AC250V5A Remote control/ Alarm |
2 |
Communication |
RS485 Interface M0DBUS-RTU |
1 |
3..Partes técnicos
|
Parameters |
|||
Precision Grade |
Electric quantity measurement 0.5, active energy, reactive energy 0.5S, analogue output 0.5 . |
|||
Display |
12-bit LED display |
|||
Signal Input |
Network |
Three-phase four wires Y34/ three-phase three wiresV33 |
||
Voltage |
Rated value |
AC380V / AC100V |
||
Over load |
Continuous:1.2 times and instantaneous: 2 times (10 seconds) |
|||
Power Consumption |
< 0.4VA |
|||
Impedance |
>300kΩ |
|||
Current |
Rated value |
AC5A / AC1A |
||
Overload |
Continuous:1.2 times and instantaneous: 10 times (5 seconds) |
|||
Power Consumption |
< 0.4 VA |
|||
Impedance |
<20 mΩ |
|||
Frequency |
45~65 Hz |
|||
Power Supply |
Working range |
AC/DC 80~270V |
||
Power Consumption |
< 5VA |
|||
Function Module |
Energy Pulse |
Passive optical coupler collector output and fixed pulse width 80mS±20% |
||
Communication Interface |
Two-way RS485 communication interface,MODUBS-RTU communication protocol; communication speed 1200~19200 and check mode N 81,E81 and O 81; |
|||
Transmission Output |
0/4~20mA or 0~5/10V transmission output; can be programmed to set transmission item and corresponding value |
|||
Relay |
Can be converted into remote control/ alarm relay output; Capacity 5A/250VAC 5A/30VDC; |
|||
Telemetry Switch |
Passive contact node input; programmable alarm output; |
|||
Operating Environment |
in the place at -10-55 °C,with relative humidity<93% and no corrosive gas with the altitude< 2500 M |
|||
Safety |
Insulation |
Signal, power supply, output terminal resistance to case> 100MΩ |
||
Withstand Voltage |
Signal input, power supply and output gas > AC2kV |
|||
External dimension |
Outline Dimension |
96×96mm |
||
Cutout Dimension |
91×91mm |
Grupos de Producto : Medidor de potencia
Premium Related Products